Part No: 202670
Bowman intercoolers / charge air heat exchangers are suitable for cooling both marine engines and land based engines, including: gensets, fire pumps and co-generation equipment. GL140-4076-2 Charge... Read more
Bowman intercoolers / charge air heat exchangers are suitable for cooling both marine engines and land based engines, including: gensets, fire pumps and co-generation equipment. GL140-4076-2 Charge air coolers are also suitable for use in engine testing and development programs.
This Bowman GL140 three pass intercooler is designed to give increased fuel efficiency and engine power when used in conjunction with a turbo charger.
Please Note: the figures listed in the "Specific Information" are based on Air temperature from 180°C to 50°C at 1.75 Bar G and using water temperature at 20°C.
Heat rejection: 40 kW
Application | Cummins 6BTA |
Flow Rate Description | Charge Air Flow: 15.4kg per minute |
Height Description | 220mm |
Length | 502mm |
Temperature Range | Maximum Air Inlet Temp: 250°C |
Width | 170mm |
Brand | Bowman |
Suitable For | Cummins |
Country of Origin | United Kingdom |
Connections Description | Water: 1-1/2" BSP, Air: 76mm |
Cooling Water Flow | 140 litres per minute |
Dimensions | Distance between fixing hole centres: 108mm |
Fixing Hole Size | M10 x 15 |
Maximum Horsepower Description | 230HP (175kW) |
Model | GL140-4076-2 |
Pressure Drop | Air: 7.4kpa, Water: 24kpa |
£1,177.51